Table 6
The electrical load (daily load demands) data for the health facility in Table 5.
Time | Daily load demands | Total energy (Wh/d) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
||||||||||||||
RV | GPR | Centrifuge | Microscope | BCA | HA | CD4 Machine | Radio & Phone | Notebook Computer | Fan | ME | Interior Lighting | Security & Pathway Lighting | ||
0.00–0.59 | 24 | 90 | 114 | |||||||||||
1.00–1.59 | 24 | 90 | 114 | |||||||||||
2.00–2.59 | 60 | 24 | 90 | 174 | ||||||||||
3.00–3.59 | 60 | 24 | 90 | 174 | ||||||||||
4.00–4.59 | 24 | 90 | 114 | |||||||||||
5.00–5.59 | 24 | 90 | 114 | |||||||||||
6.00–6.59 | 150 | 24 | 90 | 264 | ||||||||||
7.00–7.59 | 60 | 24 | 84 | |||||||||||
8.00–8.59 | 60 | 30 | 30 | 24 | 144 | |||||||||
9.00–9.59 | 60 | 40 | 88 | 30 | 125 | 100 | 24 | 467 | ||||||
10.00–10.59 | 60 | 150 | 40 | 88 | 200 | 125 | 100 | 24 | 787 | |||||
11.00–11.59 | 60 | 150 | 484 | 40 | 200 | 125 | 100 | 24 | 1183 | |||||
12.00–12.59 | 484 | 40 | 88 | 230 | 200 | 125 | 100 | 24 | 1291 | |||||
13.00–13.59 | 484 | 40 | 88 | 230 | 200 | 125 | 100 | 24 | 1291 | |||||
14.00–14.59 | 484 | 40 | 230 | 125 | 100 | 24 | 1003 | |||||||
15.00–15.59 | 230 | 30 | 125 | 100 | 24 | 509 | ||||||||
16.00–16.59 | 30 | 125 | 24 | 179 | ||||||||||
17.00–17.59 | 30 | 125 | 60 | 215 | ||||||||||
18.00–18.59 | 60 | 125 | 60 | 90 | 335 | |||||||||
19.00–19.59 | 60 | 125 | 60 | 90 | 335 | |||||||||
20.00–20.59 | 60 | 150 | 125 | 60 | 90 | 485 | ||||||||
21.00–21.59 | 150 | 125 | 60 | 90 | 425 | |||||||||
22.00–22.59 | 24 | 90 | 114 | |||||||||||
23.00–23.59 | 24 | 90 | 114 | |||||||||||
Total | 600 | 750 | 1936 | 240 | 352 | 920 | 800 | 60 | 120 | 1625 | 700 | 756 | 1170 | 10029 |